Home Products News Contact Us
Home > Supports > Diesel Generators > Shangchai Generator SC4H95D2 Technical Parameters

Shangchai Generator SC4H95D2 Technical Parameters

Oct. 15, 2019

Want to know about Shangchai generator technical parameters? This article will show you the detailed data about SC4H95D2 engine model of Shangchai generator.

◎ POWER RATING

Engine Speed

Type of  Operation

Engine Power

rpm

kW

Ps

1500

Prime Power

62

85

Stanby Power

68

95

1. The engine performance is as per GB/T2820
2. Ratings are based on GB/T1147.1

3. Prime power is available for an unlimited number of hours per year in a variable load application. The permissible average power output over 24 hours of operation shall not exceed 80% of the standby power rating.

4. Standby power is available in the even of a utility power outage or under test conditions for up to 200 hours of operation per year. The permissible average power output over 24 hours of operation shall not exceed 80% of the standby power rating,

 

◎ SPECIFICATIONS

◎ FUEL CONSUMPTION

ㅇEngine Model

SC4H95D2

ㅇPower

L/h

ㅇEngine Type

In-line, 4 strokes, water-cooled, 4 valves

25%

4.2


Turbo charged

50%

7.5

ㅇCombustion type

Direction injection

75%

11.0

ㅇCylinder Type

Dry liner

100%

14.8

ㅇNumber of cylinders

4

110%

  16.4

ㅇBore × stroke

105(4.14) × 124(4.89) mm(in.)



ㅇDisplacement

4.3(262.4) L(in3)



ㅇCompression ratio

17.3 : 1



ㅇFiring order

1-3-4-2

◎ FUEL SYSTEM


ㅇInjection timing

13.5°BTDC

ㅇInjection pump

Beiyou in-line "AD" type

ㅇDry weight

Approx.450kg (992.1 lb)

ㅇGovernor

Electric type

ㅇDimension

1012×723×1102 mm

ㅇFeed pump

Mechanical type

  (L×W×H)

(39.9×28.5×43.4in.)

ㅇInjection nozzle

Multi hole type

ㅇRotation

Counter clockwise viewed from Flywheel

ㅇOpening pressure

250 kg/cm2 (3556 psi)

ㅇFly wheel housing

SAE NO.3

ㅇFuel filter

Full flow cartridge type

ㅇFly wheel

SAE NO. 11.5

ㅇUsed fuel

Diesel fuel oil





◎ MECHANISM

◎ LUBRICATION   SYSTEM

ㅇType

Over head valve

ㅇLub. Method

Fully forced pressure feed type

ㅇNumber of valve

Intake 2, exhaust 2 per cylinder

ㅇOil pump

Gear type driven by crankshaft

ㅇValve lashes at cold

Intake  0.25mm (0.0099 in.)

ㅇOil filter

Full flow, cartridge type


Exhaust  0.50mm (0.0197 in.)

ㅇOil pan capacity

High level 13 L  ( 3.4 gal.)




Low level 11 L  ( 2.9 gal.)

◎ VALVE TIMING

ㅇAngularity limit

Front down 25 deg.


   Opening         Close


Front up 35 deg.

ㅇIntake valve

20.9°BTDC    44.9°ABDC


Side to side 35 deg.

ㅇExhaust valve

51.7°BBDC    11.7°ATDC

ㅇLub. Oil

Refer to Operation Manual





◎ COOLING SYSTEM

◎ ENGINE DATA

ㅇCooling method

Fresh water forced circulation

ㅇWater flow

117liters/min /1500 rpm

ㅇWater capacity

6.8L ( 1.8 gal.)

ㅇHeat rejection to coolant

8.9kcal/sec /1500 rpm

 (engine only)




ㅇPressure system

Max. 0.5 kg/cm2   ( 7.11 psi)

ㅇAir flow

4.7m3/min /1500 rpm

ㅇWater pump

Centrifugal type driven by belt

ㅇExhaust gas flow

10.4m3/min /1500 rpm

ㅇWater pump Capacity

117liters( 30.9 gal.)/min at 1,500 rpm (engine

ㅇExhaust gas temp.

600 °C /1500 rpm

ㅇThermost

Wax-pellet type

ㅇMax. permissible restrictions



Opening temp. 82°C

 Intake system

3 kPa  (initial)


Full open temp. 95°C

 

6 kPa (final)

ㅇCooling fan

Blower type, plastic

  Exhaust system

6 kPa (max)


550 mm diameter, 9 blades

ㅇMax. permissible altitude

2000 m









◎ ELECTRICAL SYSTEM

◆ CONVERSION TABLE

ㅇCharging generator

24V×55A  

in. = mm × 0.0394

lb/ft = N.m × 0.737

ㅇVoltage regulator

Built-in type IC regulator

PS = kW × 1.3596

U.S. gal = L × 0.264

ㅇStarting motor

24V×4.5kW

psi = kg/cm2 × 14.2233

kW = 0.2388 kcal/s

ㅇBattery Voltage

24V

in3 = L × 61.02

lb/PS.h = g/kW.h × 0.00162

ㅇBattery Capacity

120 AH

hp = PS × 0.98635

cfm = m3/min × 35.336



lb = kg × 2.20462


 

Shangchai engine.png


Maybe You Also Like Silent Generator.

Silent generator

Contact Us

  • Add.: No. 10 Kechuang Road, High tech Zone, Nanning, Guangxi, China
  • Tel.: +86 771 5805 269
  • Fax: +86 771 5805 259
  • Cellphone: +86 134 8102 4441
                    +86 138 7819 8542
  • E-mail: [email protected]
Follow Us

Copyright © Guangxi Dingbo Generator Set Manufacturing Co., Ltd. All Rights Reserved | Sitemap

Update cookies preferences

generator set:

Emergency vs Standby Generator: What’s The Difference? Commercial Generators Trailer Mounted Water Pumps for Sale
Contact Us