Home Products News Contact Us
Home > Products > Generator Sets > Volvo > 203kVA/163kW Volvo Diesel Generator Set
203kVA/163kW Volvo Diesel Generator Set

203kVA/163kW Volvo Diesel Generator Set

Standard Features 

1. Engine: Volvo TAD840GE-B

2. Radiator 50℃ max

3. Fans are driven by belt, with safety guard

4. 24V charge alternator

5. Dry type air filter, fuel filter, oil filter

6. Alternator: single bearing alternator

7. IP23, insulation class H/H

8. Main line circuit breaker

9. Standard control panel

10. Absorber

11. Muffler

12. User manual


Diesel Engine Data
Manufacturer:Volvo
Model:TAD840GE-B
Prime Power:177kW
Standby Power:194kW
Rated Speed:1500(r/min)
Cycle:4 stroke
Cylinder Arrangement:6 in-line
Displacement:7.7L
Bore and Stroke:110*135(mm)
Compression Ratio:17.5:1
Governor Type:Electronic governor
Start battery voltage:24V DC


Air Intake System
Air Intake System:Turbocharged
Max Intake Restriction:/
Air Flow Rate:/
Exhaust air flow/


Exhaust System
Exhaust Gas Flow:/
Exhaust Temperature:/
Max Back Pressure:/


Fuel System
Fuel System:Common Rail System
100% ( Prime Power) Load:/
50% ( Prime Power) Load:/


Oil System
Total lubrication system capacity:/
Total lubrication system capacity:/


Cooling System
Cooling Way:Water-cooled
Coolant Capacity-engine only/
Maximum coolant temperature - engine out:/


Alternator Data

Manufacturer:LEROY SOMER/ STAMFORD/ SIEMENS/ MARATHON/ ENGGA / KEPU
Excitation Mode:Brushless and self- exciting
Number of phase and Access Act:3-phase 4-wire
Connecting Type:"Y" type connecting
Alternator Capacity:163kW/203kVA 
Alternator Efficiencies:90%
Overload:(PRP)110% load can run 1h
Protection Level:IP22-IP23
Insulation Class, Temperature Rise:H/H
Telephone Influence Factor (TIF):<50
THF:<2%
Voltage Regulation, Steady State:≤±1%
Air Cooling Flow:0.514m3/s
Altitude:≤1000m


Genset Electrical Performance

Voltage Regulation:≥±5%
Voltage Regulation, Stead State:≤±1%
Sudden Voltage Warp (100% Sudden Reduce):≤+25%
Sudden Voltage Warp (Sudden Increase):≤-20%
Voltage Stable Time (100% Sudden Reduce):≤6S
Voltage Stable Time (Sudden Increase):≤6S
Frequency Regulation, Stead State:≤5%
Frequency Waving:≤1.5%
Sudden Frequency Warp (100% Sudden Reduce ):≤+12%
Sudden Frequency Warp (Sudden Increase):≤-10%
Frequency Recovery Time (100% Sudden Reduce):≤5S
Frequency Recovery Time (Sudden Increase):≤5S



Options

Engine

Alternator

Heater 2KW & 4KW

Anti Condensation Heater

Battery Charger 3.5A & 7A

Permanent Magnet Generator(PMG)

Water Separator

Drop CT(For Paralleling)

Daily Fuel Tank


Fuel Level Sensor


Control System

Others

Remote Control Panel

Rainproof Type

Auto Transfer Switch (ATS)

Soundproof Type

Paralleling System

Trailer Type

Open Type

Overall Size

Weight

2650(mm) *1010(mm) *1650(mm)

1550(kg)

Cummins 82GFg

Soundproof Type

Overall Size

Weight

3000(mm) *1240(mm) *1790(mm)

1800(kg)


Cummins generator

Standard Control Panel
standard control panel

Dingbo Standard Control Panel uses micro processing technique integrating digital, intelligent and network techniques which can carry out functions including auto start/stop, data measure, alarming. The controller uses LCD display, optional Chinese and English display interface with operation easy and reliable. It can be widely used in all types of generator automatic control system for compact structure, advanced circuits, simple connections and high reliability


Auto Module Control Panel
auto module

Auto Module Control Panel is the configuration for nobody on duty controlling generators. This kind of panel adopts auto module control system, with large LCD display to show the menu. Features: 6110 can receive remote output signal from ATS and realize auto start and stop of generators. 6310 can realize all functions of 6110, add RS232 interface which can communicate with PC to realize remote operation. 6410 Auto Mains Failure controller, can realize all functions of 6310, furthermore can detect ATS and control directly.

Auto Parallel Control Panel
genset auto parallel controller

This new automatic parallel system adopts intelligent modules, inserted and folded installed, no need the peripheral relay and logic circuit. The main switch adopts electronic breaker or frame breaker, combined together with the generator, which is very reliable. One generator, one panel. The panel can be used both for singly and parallel. It is only need to parallel generator with such panel when the capability needs to be enlarged in the future.



440KW Volvo Generator Set 415V 3Phase 60Hz Frequency Volvo Engine With Stanford Altornator
378kVA/302kW Volvo Diesel Generator Set
520KW Volvo Generator Set 415V 220V 3Phase 50/60Hz frequency Volvo Engine With Stanford Altornator

Contact Us

  • Add.: No. 10 Kechuang Road, High tech Zone, Nanning, Guangxi, China
  • Tel.: +86 771 5805 269
  • Fax: +86 771 5805 259
  • Cellphone: +86 134 8102 4441
                    +86 138 7819 8542
  • E-mail: [email protected]
Follow Us

Copyright © Guangxi Dingbo Generator Set Manufacturing Co., Ltd. All Rights Reserved | Sitemap

Update cookies preferences

generator set:

Emergency vs Standby Generator: What’s The Difference? Commercial Generators Trailer Mounted Water Pumps for Sale
Contact Us