For modern communication equipment, it is necessary to ensure both the normal operation of the equipment and the normal operation of its operating environment. Under normal circumstances, the AC power required for the operation of these devices is mainly provided by the power department. However, when the power department conducts normal maintenance or power outages occur due to natural disasters or man-made disasters, the property owners must rely on their own standby diesel generator sets for power supply to ensure the normal operation of communication equipment. Many people may still be quite unfamiliar with mechanical equipment such as diesel generator sets. Although they are closely related to people's lives, they are not easily accessible. Today, Guangxi Dingbo Power, a diesel generator brand manufacturer, will popularize 10 basic common sense about diesel generator sets for everyone.


standby genset


1.Why do we require customers to install the exhaust pipe of the diesel generator set with a downward slope of 5 - 10 degrees?

Mainly to prevent rainwater from entering the exhaust pipe, which could lead to major accidents.

 

2.Why is the standard outlet voltage of the generator 400V instead of 380V?

Because there is a voltage drop loss in the line after the power outlet.

 

3.Why do new machines need to have their engine oil and oil filters replaced after being used for a period of time?

During the running-in period of a new machine, impurities will inevitably enter the oil pan, causing physical or chemical changes to the engine oil and oil filter.

 

4.What are the six basic systems included in a diesel generator set?

(1) Engine oil lubrication system; (2) Starting system; (3) Exhaust system; (4) Cooling and heat dissipation system; (5) Control and protection system; (6) Fuel system

 

5.What is the function of the manual oil pump and exhaust bolt usually installed on a diesel engine?

They are used to remove air from the fuel pipe before starting the engine.

 

6.How is the automation level of diesel generator sets classified?

Manual, self-starting, self-starting with automatic mains transfer switchgear, long-distance three remote controls (remote control, remote measurement, remote monitoring)

 

7.Why do we recommend that customers use the engine oil recommended by professional companies during the sales process?

Engine oil is the blood of the engine. Using professional engine oil can lubricate and dissipate heat for key components such as the bearing bushes and gears of diesel generators, reducing wear and extending the service life. If inferior engine oil is used, it can lead to serious accidents such as bearing bushes seizing, gears breaking teeth, and crankshaft deformation and fracture, and may even result in the complete scrapping of the engine.

 

8.A generator set has stable voltage and frequency after being loaded, but the current is unstable. Where is the problem?

The problem should lie in the unstable load of the customer. There is no problem with the quality of the generator.

 

9.When installing the engine oil filter, diesel filter, and oil-water separator of a diesel generator set, it is not advisable to use tools to screw these three filters too tightly. Just screw them by hand until there is no oil leakage. Why?

Because if they are screwed too tightly, under the action of oil soaking and the temperature rise of the machine body, the sealing ring will expand thermally, generating great stress. This can cause damage to the filter housing or the separator housing itself. More seriously, it can lead to damage to the machine body nuts, making them irreparable.

 

10.Different brands of diesel generator sets share a general formula for calculating current:

I = P/(√3 Ucos φ) (Current = Power (watts) / (√3 * 400 (volts) * 0.8)). The simplified formula is: I (A) = Rated power of the unit (KW) * 1.8

 

As a professional diesel generator manufacturer, we always insist on using first-class talents to build a first-class enterprise, create first-class products, create first-class services, and strive to build a first-class domestic enterprise. If you would like to get more information welcome to contact us via [email protected].

Contact Us

  • Add.: No. 10 Kechuang Road, High tech Zone, Nanning, Guangxi, China
  • Tel.: +86 771 5805 269
  • Fax: +86 771 5805 259
  • Cellphone: +86 134 8102 4441
                    +86 138 7819 8542
  • E-mail: [email protected]
Follow Us

Copyright © Guangxi Dingbo Generator Set Manufacturing Co., Ltd. All Rights Reserved | Sitemap

Update cookies preferences

generator set:

Emergency vs Standby Generator: What’s The Difference? Commercial Generators Trailer Mounted Water Pumps for Sale
Contact Us