Installation Standards for Fire Emergency Lights in Diesel Generator Rooms

Sep. 05, 2025

Emergency lighting is designed to ensure the continuation of normal activities when the regular lighting power supply fails. Fire emergency lights must be installed in emergency diesel generator rooms.


diesel generator manufacturer


Installation Locations for Fire Emergency Lights in Diesel Generator Rooms

1.Enclosed stairwells, smoke-proof stairwells and their antechambers, fire elevators and their antechambers.

2.Power distribution rooms, fire control rooms, automatic generator rooms, fire pump rooms, smoke control and exhaust control rooms, battery rooms for fire-fighting power supply, main telephone rooms, and rooms where personnel need to stay to extinguish fires in case of a fire.

3.Exhibition halls and business halls with a floor area exceeding 1500㎡ per floor in auditoriums, studios with a building area exceeding 2000㎡, and crowded basements with a building area exceeding 300㎡.

4.Escape routes (safe exit passages) in public buildings and internal corridors with a length exceeding 20 meters.

 

Installation Standards for Fire Emergency Lights in Generator Rooms

1.In modern engineering design, fire emergency lights should preferably be powered by a dedicated feeder circuit per floor to facilitate daily maintenance and management.

2.To ensure the reliability of the power supply for fire emergency lights, if conditions permit, it should be supplied by the low-voltage emergency bus section of the substation. That is, when a diesel generator set is used as the emergency power source, the lights will continue to be powered as long as the generator is in operation.

3.Fire emergency lights are recommended to be installed at a low position, i.e., near or at ground level. In a fire, there is less smoke and more oxygen near the ground, and people usually escape by bending over or crawling. Localized high-illumination lighting at a low position is more effective than average illumination from a high installation.

4.Fire emergency lights must leave the factory in a discharged state. They must be charged for 20 hours before use to allow discharge.

5.Fire emergency lights should undergo regular performance checks. Every half a month or month, conduct a continuous switch test to check their circuit conversion and battery emergency functions, and perform discharge to extend the battery life.

6.Fire protection for power distribution lines of fire emergency lights must be ensured. When concealed, they should be laid in non-combustible structures with a protective layer thickness of not less than 30mm; Wear metal pipes when applying openly, and apply fireproof coating or other fireproof measures outside the steel pipes; The line adopts fire-resistant cables or fire-resistant cables and wires.

 

Dingbo Power has advanced testing equipment, modern production technology, professional manufacturing technology, perfect quality management system, and strong technical research and development capabilities. It can provide 3KW~2500KW various specifications of ordinary, automatic, four protection, automatic switching, low noise and mobile generator sets, high quality and low energy consumption to meet the diverse power needs of customers, and can also meet users with different voltages and different frequencies. It is required to create a parallel power supply system for multiple units. If you are interested in our product or any question on generator, welcome to send email to [email protected].

Contact Us

  • Add.: No. 10 Kechuang Road, High tech Zone, Nanning, Guangxi, China
  • Tel.: +86 771 5805 269
  • Fax: +86 771 5805 259
  • Cellphone: +86 134 8102 4441
                    +86 138 7819 8542
  • E-mail: [email protected]
Follow Us

Copyright © Guangxi Dingbo Generator Set Manufacturing Co., Ltd. All Rights Reserved | Sitemap

Update cookies preferences
Contact Us