Sep. 20, 2019


Auto Module Control Panel is the configuration for nobody on duty controlling generators. This kind of panel adopts auto module control system, with large LCD display to show the menu, such as SmartGen controller.


Features: 

1. SmartGen 6110 can receive remote output signal from ATS and realize auto start and stop of generators.

2. SmartGen 6310 can realize all functions of 6110, add RS232 interface which can communicate with PC to realize remote operation. 

3. SmartGen 6410 Auto Mains Failure controller, can realize all functions of 6310, furthermore can detect  ATS and control directly.


SmartGen controller


The alarm of diesel generator controller is not the amount of stop alarm, which does not affect the normal operation of diesel generator. When the alarm occurs, the unit will not stop, and when the alarm conditions do not exist, the amount of warning will automatically disappear. 


Today Starlight manufacturer mainly shares alarm codes for diesel generator SmartGen controller, as follows:


No.

Name

Scope of action

Description

1

Generation overcurrent warning


Always effective

When the controller detects that the current of the generator set is more than the overcurrent warning threshold value, the controller sends out warning alarm signal and displays warning information on the LCD screen.

2

Outage failure warning

After generator set stop stable and the delay is over.


After the generator set stop stable and the delay is over, if the generator output is electrified or the oil pressure is not zero, the controller sends out a warning and alarm signal. The warning message is displayed on the LCD screen of colleagues.

3

Low fuel level warning

Always effective

When the controller detects that the fuel level of the generator set is less than the set  threshold value, the controller sends out warning and alarm signals, and the warning information is displayed on the LCD screen.

4

Charge failure warning

From start-up idle to stop idle

When the controller detects that the charger voltage value of the generator set is less than the set threshold value, the controller sends out warning and alarm signals, and the warning information is displayed on the LCD screen at the same time.

5

Speed signal loss warning

From successful start to stop idling

When the controller detects that the speed of the generator is equal to zero, the controller sends out an early warning signal, and the warning information is displayed on the LCD screen at the same time.

6

Starting battery undervoltage warning

Always effective

When the controller detects that starting battery voltage is less than the set threshold value, the controller sends out warning signal, the warning information is displayed on the LCD screen.

7

Start battery overvoltage warning

Always effective

When the controller detects that the starting battery voltage is more than the set threshold value, the controller sends out warning signal, and the warning information is displayed on the LCD screen.

8

power generation break-brake failure

Always effective

When break-brake delay is over, the controller did not detect that switch break-brake signal,the controller sends out warning signal,and the warning information is displayed on the LCD screen.

9

Auxiliary input 1-9 warning

User-defined valid range

When the controller detects that auxiliary 1-9 input warns input, the controller sends out warning signal,and the warning information is displayed on the LCD screen.

10

Time to maintain


Always effective

When the cumulative running time of the engine exceeds the set maintenance time or the cumulative date exceeds the set number of days, the controller sends out warning signal, and the warning information is displayed on the LCD screen.

11

Synchronization failure

When synchronization is valid

When at the set synchronization time, the controller did not detect synchronization signal, the controller sends out warning signal,and the warning information is displayed on the LCD screen.

12

Generation phase sequence error

When generation is effective.

When the controller detects generation phase sequence is not correct( correct phase sequence is L1, L2, L3), the controller sends out warning signal,and the warning information is displayed on the LCD screen.

13

Generatrix phase sequence error

When generatrix is effective.

When the controller detects the incorrect phase sequence of the parent row( correct phase sequence is L1, L2, L3), it sends out a warning signal of phase sequence error, the warning information is displayed on the LCD screen.

14

MSC data is incorrect.

Always effective

When the controller detects MSC data is incorrect, it sends out a warning signal,  and the warning information is displayed on the LCD screen.  

15

MSC modules is few.

Always effective

If the number of parallel units is less than the min. number of parallel units set, the controller sends out a warning signal, and the warning information is displayed on the LCD screen.

16

ECU warning

Always effective

When the engine CAN bus receives an error message from an engine ECU, it sends out a warning signal,and the warning information is displayed on the LCD screen.

17

The load current is unbalanced.

When power generation has been switched on.

When the controller defects load current imbalance is more than the set threshold value, it sends out a warning signal,  and the warning information is displayed on the LCD screen.

18

Over speed warning

Always effective

When the controller defects engine speed value is more than the set threshold value, it sends out a warning signal,  and the warning information is displayed on the LCD screen. 


Above is the alarm codes for SmartGen genset controller, SmartGen controller is common used for diesel generator set. 

Contact Us

  • Add.: No. 10 Kechuang Road, High tech Zone, Nanning, Guangxi, China
  • Tel.: +86 771 5805 269
  • Fax: +86 771 5805 259
  • Cellphone: +86 134 8102 4441
                    +86 138 7819 8542
  • E-mail: [email protected]
Follow Us

Copyright © Guangxi Dingbo Generator Set Manufacturing Co., Ltd. All Rights Reserved | Sitemap

Update cookies preferences

generator set:

Emergency vs Standby Generator: What’s The Difference? Commercial Generators Trailer Mounted Water Pumps for Sale
Contact Us