1. 200KW 250KVA Shangchai diesel generator SC9D340D2 engine technical parameters is given below:


◎POWER RATING


Engine Speed

Type of Operation

Engine Power

rpm

kW

Ps

1500

Prime Power

228

310

Stanby Power

250

340


1. Standard & certificate: 

GB/T2820

GB/T1147.1

ISO/TS16949:2002 Quality Management System

ISO14001 Environment Management System

OHSAS18001 Occupation Health and Safety Management System

LL-C Certificate

2. Prime power is available for an unlimited number of hours per year in a variable load application. The permissible average power output over 24 hours of operation shall not exceed 80% of the prime power rating.

3. Standby power is available in the even of a utility power outage or under test conditions for up to 200 hours of operation per year. The permissible average power output over 24 hours of operation shall not exceed 80% of the standby power rating.

 

◎ SPECIFICATIONS

◎ FUEL CONSUMPTION

ㅇEngine Model

SC9D340D2

ㅇPower

lit/hr

ㅇEngine Type

In-line, 4 strokes, water-cooled, 4 valves, Turbo charged air-to-air intercooled

25%

14.7



50%

27.3

ㅇCombustion type

Direction injection

75%

40.8

ㅇCylinder Type

Wet liner

100%

54.1

ㅇNumber of cylinders

6

110%

59.6

ㅇBore × stroke

114(4.49) × 144(5.67) mm(in.)



ㅇDisplacement

8.82 (538.2) lit.(in3)



ㅇCompression ratio

16.5 : 1



ㅇFiring order

1-5-3-6-2-4

◎ FUEL SYSTEM


ㅇInjection timing

8.5°BTDC

ㅇInjection pump

Longkou in-line "P" type

ㅇDry weight

Approx.840kg (1852b)

ㅇGovernor

Electric type

ㅇDimension

1578×778×1290mm

ㅇFeed pump

Mechanical type

  (L×W×H)

(62.2×30.7×50.8 in.)

ㅇInjection nozzle

Multi hole type

ㅇRotation

Counter clockwise viewed from Flywheel

ㅇOpening pressure

250 kg/cm2 (3556 psi)

ㅇFly wheel housing

SAE NO.2

ㅇFuel filter

Full flow, cartridge type

ㅇFly wheel

SAE NO. 11.5

ㅇUsed fuel

Diesel fuel oil





◎ MECHANISM

◎ LUBRICATION SYSTEM

ㅇType

Over head valve

ㅇLub. Method

Fully forced pressure feed type

ㅇNumber of valve

Intake 2, exhaust 2 per cylinder

ㅇOil pump

Gear type driven by crankshaft

ㅇValve lashes at cold

Intake 0.30mm (0.0118 in.)

ㅇOil filter

Full flow, cartridge type


Exhaust 0.55mm (0.0217 in.)

ㅇOil pan capacity

High level 25 liters ( 6.6 gal.)

Low level 22 liters (5.8 gal)



ㅇAngularity limit

Front down 25 deg.

Front up 35 deg.

Side to side 35 deg.

◎ VALVE TIMING


Opening        

Close

ㅇIntake valve

29.5°BTDC

42.5°ABDC



ㅇExhaust valve

69.5°BBDC

34.5°ATDC

ㅇLub. Oil

Refer to Operation Manual





◎ COOLING SYSTEM

◎ ENGINEERING DATA

ㅇCooling method

Fresh water forced circulation

ㅇWater flow

200 liters/min @1,500 rpm

ㅇWater capacity (engine only)

12 liters ( 3.17 gal.)

ㅇHeat rejection to coolant

20.35kcal/sec @1,500 rpm



ㅇHeat rejection to CAC10.2 m3/min @1,500 rpm

ㅇPressure system

Max. 0.5 kg/cm2 ( 7.11 psi)

ㅇAir flow

18.6 m3/min @1,500 rpm

ㅇWater pump

Centrifugal type driven by belt

ㅇExhaust gas flow

41 m3/min @1,500 rpm

ㅇWater pump Capacity

200 liters( 52.8 gal.)/min at 1, 500 rpm(engine)

ㅇExhaust gas temp.

600 °C @1,500 rpm

ㅇThermostat

Wax-pellet type

Opening temp. 82°C

Full open temp. 93°C

ㅇMax. permissible restrictions


Intake system

3 kPa initial

6 kPa final

ㅇCooling fan

Blower type, plastic

762 mm diameter, 10 blades

Exhaust system

6 kPa max

ㅇMax. permissible altitude

2,000 m





◎ ELECTRICAL SYSTEM

◆ CONVERSION TABLE

ㅇCharging generator

28V×55A

in. = mm × 0.0394

lb/ft = N.m × 0.737

ㅇVoltage regulator

Built-in type IC regulator

PS = kW × 1.3596

U.S. gal = lit. × 0.264

ㅇStarting motor

24V×7.5kW

psi = kg/cm2 × 14.2233

kW = 0.2388 kcal/s

ㅇBattery Voltage

24V

in3 = lit. × 61.02

lb/PS.h = g/kW.h × 0.00162

ㅇBattery Capacity

180 AH

hp = PS × 0.98635

cfm = m3/min × 35.336



lb = kg × 2.20462



Shangchai engine SC9D340D2.jpg


Note: As one of leading manufacturers of diesel generator in China, we can provide 50KW to 1600KW diesel generating sets with Shangchai engine. The genset style includes open generator, soundproof generator, trailer generator, portable generator and containerized genset, etc. The unit can be equipped with ATS and base fuel tank. Alternators we can supply original Stamford, Siemens, Leroy-somer, Marathon, Engga, and our own brand Starlight alternator. 


Alternator basic data is given below:



Alternator Data

Output Power (KW)

200KW

Structure

One-piece

Excitation type

Brushless Self Excitation

Overload Capacity

10% overload for one hour

Insulation Class

H

Short-time Current

150%10S

Protection Class

IP22

Mode of Connection

3-phase, 4-line, neutral ground

Rated Voltage

400V

Power Factor

0.8Lag

Rated Frequency50 HzRated Speed1500rpm


Note: Control Module you can select Deep Sea (UK) - DSE7320 or SmartGen (China) - HGM6110


DSE7320 control module

Contact Us

  • Add.: No. 10 Kechuang Road, High tech Zone, Nanning, Guangxi, China
  • Tel.: +86 771 5805 269
  • Fax: +86 771 5805 259
  • Cellphone: +86 134 8102 4441
                    +86 138 7819 8542
  • E-mail: [email protected]
Follow Us

Copyright © Guangxi Dingbo Generator Set Manufacturing Co., Ltd. All Rights Reserved | Sitemap

Update cookies preferences

generator set:

Emergency vs Standby Generator: What’s The Difference? Commercial Generators Trailer Mounted Water Pumps for Sale
Contact Us