Thermal Test of Synchronous Generator

Jan. 08, 2026

The function of the thermal test of a synchronous generator set is to obtain the temperature values of components such as motor windings, collector rings, commutators, and bearings when they operate under specified working conditions and reach a stable temperature rise through the test. It can inspect whether the insulation materials and production processes of the tested motor meet the requirements, enabling the motor to work normally and better prolong the service life of the unit.


diesel genset


There are two thermal test methods for synchronous generators: direct loading method and indirect loading method. The direct loading method can be further divided into the full-load direct loading method and the reduced-load direct loading method. The indirect loading method can be divided into the low power factor loading method and the no-load short-circuit method.

 

1.Direct Loading Method

When conducting the test using the synchronous feedback direct loading method, two motors need to be connected mechanically and electrically. When the tested motor operates as a generator, the auxiliary motor operates as a motor, and vice versa, which can be used for the thermal tests of synchronous generators and motors simultaneously. During operation, the electrical energy generated by the generator is fed back to the motor, and there are two methods to provide the energy consumed by the above two motors as follows:

Method 1: Provided by a third synchronous motor. When coupled with a coupling, this motor should be double-shaft extended, and its rated speed should be the same as that of the tested motor.

Method 2: Provided by a power supply. The frequency and voltage should be exactly the same as those of the tested motor, and appropriate measures need to be taken to prevent harmful electrical or mechanical transient processes when the motor reaches the rated speed.

 

2.Reduced-Load Direct Loading Method

When conducting the thermal test under reduced load, the power factor of the tested motor should be equal to or close to the rated value. After obtaining the temperature rise values of windings, iron cores, and related components at each load, plot the relationship curves between temperature rise and the square of winding current or the losses of the components. Extend these curves upward smoothly to the rated load point of the tested motor, and obtain the temperature rise value at the rated load point through the coordinates.

 

Guangxi Dingbo Generator Set Manufacturing Co.,Ltd. was founded in 1974 and is one of the earliest manufacturers of generators and diesel generator sets in China. The company has a registered capital of 218.88 million yuan. The company covers an area of 86,000 square meters and a building area of 55,000 square meters. There are more than 660 employees, including 456 professional technicians and 106 senior technicians. It has 46 sales and service outlets nationwide. The main products are diesel engines, generator sets, and diesel generators, providing users with a one-stop service of design, supply, debugging and maintenance at any time. Dingbo has always insisted on using first-class talents, building first-class enterprises, manufacturing first-class products, creating first-class services, and making every effort to build a first-class domestic enterprise. If any question please feel free to visit our website https://www.dieselgeneratortech.com/ or send email to [email protected].

Contact Us

  • Add.: No. 10 Kechuang Road, High tech Zone, Nanning, Guangxi, China
  • Tel.: +86 771 5805 269
  • Fax: +86 771 5805 259
  • Cellphone: +86 134 8102 4441
                    +86 138 7819 8542
  • E-mail: [email protected]
Follow Us

Copyright © Guangxi Dingbo Generator Set Manufacturing Co., Ltd. All Rights Reserved | Sitemap

Update cookies preferences
Contact Us