Home Products News Contact Us
Home > Supports > Diesel Engine > Parameter Settings of Volvo Engine TAD734GE

Parameter Settings of Volvo Engine TAD734GE

Oct. 18, 2019

Connecting the VODIA parameter tool

parameter tool.jpg


Function, VODIA

By using the VODIA tool (3838619) in position “Parameters, reprogramming” you can read off and adjust the parameters stated below. The VODIA tool is connected to the diagnostics connector (6-pin connector block) located beneath the “cable cover” on the left side of the engine, or by using T-diagnostic connector no. 874427. Refer to the “VODIA user guide” for help in using the tool.


Adjustable parameters

NOTE: VODIA is used to adjust parameters in CIU and EMS2. Some parameters require special authorization.


Functions


Primary control mode

Selects which regulator is to be used when there is no primary control switch.

Alternative position

“Isochronal”or“droop” characteristic

Preset position

“Isochronous”

Control gradient (Droop)

Determines the engine speed droop to be used (gradient)

Min. value

0%

Preset value

4%

Max. value

8%

Lamp test

This parameter determines if a lamp test is to be performed when the system is   started.

Alternative position

“Off” or “On”

Preset position

“On”

Idle.

Sets the idle speed.

Min. value

600 rpm

Preset value

900 rpm

Max. value

1200 rpm

Pre-heating before ignition

Selects if pre-heating is activated directly when the ignition is turned on. If the parameter “Off” has been selected, pre-heating must be activated manually via the ignition lock or pre-heater button.

Alternative position

“Off” or “On”

Preset position

“Off”

Connected to system voltage during running/stop, EMS

Stops input data to the CIU unit connected to system voltage at “run” or “stop”.

Preset position

“Stop”

Connected to system voltage during running/stop, CIU

Stops input data to the CIU unit connected to system voltage at “run” or “stop”.

Preset position

“Stop”

Idle voltage, CIU


Voltage of the throttle signal corresponding to idle at the CIU unit.

Min. value

0.3 V

Preset value

1.17 V

Max. value

1.9 V

Voltage max. rpm CIU

Voltage of the throttle signal corresponding to full throttle at the CIU unit.

Min. value

1.9   V

Preset value

4.5   V

Max. value

4.7   V

Alarm limits

Alarm limit, high coolant temperature

a warning lamp is lit at this temperature.

Min. value

95 °C

Preset value

104 °C

Max. value

103 °C

Engine protector

Engine protector coolant temperature

Determines if engine protection shall be activated in response to high coolant temperature.

A fault code is registered and the engine is shut down.

Alternative position

“Off” or “On”

Preset value

“On”

Engine protector coolant level

Determines if engine protection shall be activated in response to low coolant level.

Alternative position

“Off” or “On”

Preset value

“On”

Engine protector charge air temperature

Determines if engine protection shall be activated in response to high charge air temperature.

Alternative position

"Off" or "On"

Preset value

“On”

Engine protection, charge air pressure

Determines if engine protection shall be activated in response to high charge air pressure.

Alternative position

“Off” or “On”

Preset value

“On”

Engine protection, oil pressure

Determines if engine protection shall be activated in response to low oil pressure.

Alternative position

“Off” or “On”

Preset value

“On”

 

Engine speed regulator, adjustment


The regulator has a factory setting that has been optimized to suit the most common generator set applications. Use the VODIA tool (including EMS software), to read and adjust the P, I and D sections of the engine speed regulator. Adjustment is done to obtain more stable and even engine running, and to configure the engine for specific generating set applications.

PID = Proportional, Integrating, Differentiating

P-value amplifier (Gain), amplification of the difference between the actual value and the set value.

A reduced value (Fig. 1) gives a weaker reaction to engine speed differences. Reduce the P-value to reduce oscillations arising from large differences in speed/load application.


PID.jpg

An increased value (Fig. 2) gives a shorter response time. Increase the P section for faster compensation to large differences in engine speed/engine loading.

engine speed.jpg



I-value stabilizes (Stability), reacts to the time of the speed deviation.

A reduced value (Fig. 3) increases the time taken by the system to respond after a load change. Reduce the I section to reduce the oscillations which are caused by slow application of engine loading.

Volvo engine.jpg


An increased value (Fig 4) gives a shorter response time. Increase the I-value to provide better load response for slowly increasing loads.

D-value compensates (Derivative). Reacts to fast changes of engine speed/load.

A reduced value (Fig 4.) gives a greater sensitivity to fast changes of engine speed/load. Reduce the D-value to reduce oscillations caused by fast changes.


reduced value.jpg


An increased value (Fig. 5) gives a reduced sensitivity to fast load changes. Increase the D-value to provide a better ability to compensate for fast changes.


Volvo engine.jpg

Adjustment of PID regulator

1. Start the engine.

2. Select the “Engine with mounting and equipment” and then “Reinforcement and Stability, calibration” function groups in the VODIA tool.


regulator.jpg


3. When calibration is started, certain conditions must be met, such as that the engine must be running and must have reached a certain engine temperature.


Volvo TAD734GE.jpg


4. Select “High” or “Low”.

High: when one is far from the nominal engine speed, i.e. to improve load response.

engine speed.jpg


Low: when one is close to the nominal engine speed point, i.e. to increase stability.

engine speed.jpg


5. Run the engine at the working speed and working temperature.

In cases where the engine needs to be adjusted, in-crease or reduce the values of the P and I sections until unstable (oscillating) engine speed is obtained. Then increase/decrease the parameters until the engine speed is stable again.

6. If the engine is still unstable, increase/reduce the D section until engine speed only increases slightly when load is applied (or removed), please refer to figure 6.


load application.jpg


NOTE: The few times that the D-value may need to be adjusted include cases where the application has a flexible coupling or extremely low flywheel inertia.

7. Adjust the P and I sections again as above, if necessary.

8. Check engine response as fig. 6.

9. Repeat the procedure in the other position, “High”/“Low” if necessary.

10. To reset to factory settings, use the reset button above the PID settings.

11. Click “Continue” to finish calibration and follow the instructions to save the current settings in the control unit.


parameter settings.jpg


Frequency alteration, EMS2

The routine for altering the engine speed on the TAD734GE is not the same as for, i.e. D12. There is no system reset on the EMS2 unit, and the routine is therefore completely different.

With Volvo Penta CIU

If the engine is a 1500 rpm or 1800 rpm, the frequency selector must be OPEN when you start the adjustment. OPEN selects the primary engine speed, CLOSED selects the secondary engine speed.

Routine, with no system voltage applied:

1. Turn on the ignition with the starter key or switch. 2. Change the frequency selector (open or closed). 3. Send a stop request by pressing on the stop button.

The whole procedure (steps 1 to 3) may not take longer than 10 seconds.

Routine, with system voltage applied:

1. Send a stop request by pressing on the stop button.

2. Change the frequency selector (open or closed).

3. Send a stop request by pressing on the stop but-ton.

The whole procedure (steps 1 to 3) may not take long-er than 10 seconds.

With DCU

Turn on the ignition and change the parameter in the DCU.

With SAE J1939 (CAN)

Customers who use their own CAN bus-based control unit, must send certain messages to the engine (TAD734GE) in the same way as for the Volvo Pentas CIU, in order to change from 1500 to 1800 rpm (or vice-versa).

Routine, with no system voltage applied:

1. Turn on ECU.

2. Change the frequency selection in the

VP_STATUS-message (open or closed).

3. Send a stop request in a VP_STATUS-message.

The whole procedure (steps 1 to 3) may not take longer than 10 seconds.

Routine, with system voltage applied:

1. Send a stop request in a VP_STATUS-message.

2. Change the frequency selection in the

VP_STATUS-message (open or closed).

3. Send a stop request in a VP_STATUS-message.

The whole procedure (steps 1 to 3) may not take longer than 10 seconds.


NOTE: We are authorized as Volvo diesel generator OEM and can provide 85KVA to 750KVA power generator with Volvo engine. Volvo engine performance corresponds to ISO 3046, BS 5514 and DIN 6271. Engine speed governing in accordance with ISO 3046/IV, class A1 and ISO 8528-5 class G3. Besides, the engine complies with EU stage 2 emission legislation according to the Non Road Directive EU 97/68/EC.

Contact Us
  • Add.: Room 601, Laboratory Building, No.2 Gaohua Road, Nanning, Guangxi, China.
  • Tel.: +86 771 5805 269
  • Fax: +86 771 5805 259
  • Cellphone: +86 134 8102 4441
                    +86 138 7819 8542
  • E-mail: sales@dieselgeneratortech.com
Follow Us

Copyright © Guangxi Dingbo Power Equipment Manufacturing Co., Ltd. All Rights Reserved | Sitemap

Update cookies preferences

seokeywords:

test2
Contact Us