Diesel Generator Set Data
Genset Model: DB-240GF
Rated Power: 240kW/300kVA
Rated Current: 432A
Rated Frequency: 50(Hz)
Power Factor: 0.8(Lag)
Rated Voltage: 400/230V(customizable)
For more types, please contact us.
The 240KW 300KVA Deutz Diesel Generator Set is a high-performance industrial power solution powered by a reliable Deutz diesel engine. Designed for continuous and emergency power supply, this generator set delivers stable output, low fuel consumption, and long service life. As a professional 240KW Deutz Diesel Generator Set supplier, Dingbo provides complete generator solutions for global customers.
Original Deutz diesel engine with strong power and proven reliability
Rated power 240KW / 300KVA, suitable for heavy-duty commercial/industrial applications
Low fuel consumption and optimized combustion efficiency
Stable voltage and frequency for sensitive equipment
Easy maintenance with globally available spare parts
Genset Model: DB-240GF
Rated Power: 240KW/300kVA
Standby Power: 264kW/330kVA
Engine Brand: Deutz
Frequency: 50Hz / 60Hz
Voltage: 400V / 230V (customizable)
Phase: Three Phase
Cooling System: Water Cooled
Starting Method: Electric Start
The 240KW 300KVA Deutz Diesel Generator Set price depends on configuration options such as alternator brand, control system, enclosure type (open, silent, containerized), and OEM requirements. Dingbo offers competitive wholesale prices directly from the factory, helping distributors and project contractors reduce total procurement costs.
Contact Dingbo today to get an accurate quotation and technical proposal tailored to your project.
Dingbo supports OEM and ODM services for the custom 240KW Deutz Diesel Generator Set. From voltage and frequency customization to brand labeling and control system integration, we provide flexible solutions for different regional standards and project requirements.
OEM branding for distributors and dealers
Custom voltage and frequency options
Silent, open, or containerized generator configurations
Compliance with regional standards and applications
The Deutz 300KVA Diesel Generator is widely used in industries requiring reliable and continuous power supply, including:
Standby power for offices, hospitals, and hotels
Construction sites and infrastructure projects
Hospitals and emergency power systems
Data centers and commercial buildings
Mining, oil & gas, and remote power stations
As an experienced Deutz Diesel Generator Set supplier, Dingbo provides the 240KW Deutz Generator Set wholesale to customers worldwide, including Asia, Africa, the Middle East, South America, and Europe. We understand regional power standards and offer fast delivery and technical support for overseas projects.
Professional manufacturer and exporter of diesel generator sets
Stable supply chain and strict quality control
Competitive factory-direct pricing for B2B buyers
Strong technical support and after-sales service
Rich experience in international projects and bulk orders
If you are looking for a reliable Deutz Diesel Generator Set for Sale, Dingbo is your trusted partner. Whether for wholesale distribution, engineering projects, or customized power solutions, our team is ready to support your business.
Contact Dingbo now to receive the latest price, technical datasheet, and customized solution for the 240KW 300KVA Deutz Diesel Generator Set.
| Diesel Engine Data | ||
| Manufacturer: | DEUTZ | |
| Model: | TCD8.7 | |
| Prime/Standby Power: | 265KW/290KW | |
| Rated Speed: | 1500(r/min) | |
| Cycle: | 4 stroke | |
| Cylinder Arrangement: | 6, in line | |
| Displacement: | 8.7L | |
| Bore and Stroke: | 117*135(mm) | |
| Compression Ratio: | 17.5:1 | |
| Governor Type: | Electronic | |
| Start battery voltage: | 24V DC | |
| Air Intake System | ||
| Air Intake System: | Turbo, CAC | |
| Combustion air volume: | 1029m3/h | |
| Exhaust System | ||
| Max. exhaust back pressure | 100 mbar | |
| Max. exhaust gas temperature | 680℃ | |
| Exhaust gas flow (at above temp) | 1500 m3/h | |
| Fuel System | ||
| Fuel System: | Common rail | |
| 100%( Prime Power) Load: | 195.01g/kwh | |
| 50%( Prime Power) Load: | 196.31g/kwh | |
| Oil System | ||
| Oil capacity (sump) | 28L | |
| Max. permissible oil temperature(oil pan) | 120°C | |
| Cooling System | ||
| Cooling Way: | Water-cooled | |
| Coolant capacity (engine) | 14L | |
| Max. temperature of coolant (shutdown): | 113℃ | |
| Alternator Data | ||
| Manufacturer: | LEROY SOMER/STAMFORD/SIEMENS/MARATHON/ENGGA /Dingbo | |
| Excitation Mode: | Brushless and self- exciting | |
| Number of phase and Access Act: | 3-phase 4-wire | |
| Connecting Type: | "Y" type connecting | |
| Alternator Capacity: | 240kW/300kVA | |
| Alternator Efficiencies: | 95% | |
| Overload: | (PRP)110% load can run 1h | |
| Protection Level: | IP22-IP23 | |
| Insulation Class, Temperature Rise: | H/H | |
| Telephone Influence Factor (TIF): | <50 | |
| THF: | <2% | |
| Voltage Regulation, Steady State: | ≤±1% | |
| Altitude: | ≤1000m | |
| Genset Electrical Performance | ||
| Voltage Regulation: | ≥±5% | |
| Voltage Regulation, Stead State: | ≤±1% | |
| Sudden Voltage Warp (100% Sudden Reduce): | ≤+25% | |
| Sudden Voltage Warp (Sudden Increase): | ≤-20% | |
| Voltage Stable Time (100% Sudden Reduce): | ≤6S | |
| Voltage Stable Time (Sudden Increase): | ≤6S | |
| Frequency Regulation, Stead State: | ≤5% | |
| Frequency Waving: | ≤1.5% | |
| Sudden Frequency Warp (100% SuddenReduce): | ≤+12% | |
| Sudden Frequency Warp (Sudden Increase): | ≤-10% | |
| FrequencyRecoveryTime(100%SuddenReduce): | ≤5S | |
| FrequencyRecoveryTime(Sudden Increase): | ≤5S | |
Options | ||||||
Engine | Alternator | |||||
Heater 2KW & 4KW | Anti Condensation Heater | |||||
Battery Charger 3.5A & 7A | Permanent Magnet Generator(PMG) | |||||
Water Separator | Drop CT(For Paralleling) | |||||
Daily Fuel Tank | ||||||
Fuel Level Sensor | ||||||
Control System | Others | |||||
Remote Control Panel | Rainproof Type | |||||
Auto Transfer Switch (ATS) | Soundproof Type | |||||
Paralleling System | Trailer Type | |||||
Open Type | ||||||
Overall Size | Weight | |||||
2720(mm)*1370(mm)*2130(mm) | 2400(kg) | |||||
| ||||||
Soundproof Type | ||||||
Overall Size | Weight | |||||
4000(mm)*1800(mm)*2150(mm) | 4200(kg) | |||||
| ||||||
| Standard Control Panel | ||
![]() | Dingbo Standard Control Panel uses micro processing technique integrating digital, intelligent and network techniques which can carry out functions including auto start/stop, data measure, alarming. The controller uses LCD display, optional Chinese and English display interface with operation easy and reliable. It can be widely used in all types of generator automatic control system for compact structure, advanced circuits, simple connections and high reliability | |
| Auto Module Control Panel | |
![]() | Auto Module Control Panel is the configuration for nobody on duty controlling generators. This kind of panel adopts auto module control system, with large LCD display to show the menu. Features: 6110 can receive remote output signal from ATS and realize auto start and stop of generators. 6310 can realize all functions of 6110, add RS232 interface which can communicate with PC to realize remote operation. 6410 Auto Mains Failure controller, can realize all functions of 6310, furthermore can detect ATS and control directly. |
| Auto Parallel Control Panel | |
![]() | This new automatic parallel system adopts intelligent modules, inserted and folded installed, no need the peripheral relay and logic circuit. The main switch adopts electronic breaker or frame breaker, combined together with the generator, which is very reliable. One generator, one panel. The panel can be used both for singly and parallel. It is only need to parallel generator with such panel when the capability needs to be enlarged in the future. |
Copyright © Guangxi Dingbo Generator Set Manufacturing Co., Ltd. All Rights Reserved | Sitemap
Update cookies preferences