Standard Features


1. Engine: CCEC Cummins KTA50-G8

2. Radiator 50℃ max

3. Fans are driven by belt, with safety guard

4. 24V charge alternator

5. Dry type air filter, fuel filter, oil filter

6. Alternator: single bearing alternator

7. IP23, insulation class H/H

8. Main line circuit breaker

9. Standard control panel

10. Absorber

11. Muffler

12. User manual


Diesel Engine Data
Manufacturer:CCEC Cummins
Model:KTA50-G8
Prime/Standby Power:1200KW/1429KW 
Rated Speed:1500(r/min)
Cycle:4 stroke
Cylinder Arrangement:16 "V"
Displacement:50.3L
Bore and Stroke:159*159(mm) 
Compression Ratio:13.9:1
Governor Type:Electronic
Start battery voltage:24V DC
Air Intake System
Air Intake System:Turbo, Water/Air Cooling
Max Intake Restriction:6.35kPa
Burning Capacity:22.5m3/min
Air Flow:2160m3/min


Exhaust System
Exhaust Gas Flow:261m3/min
Exhaust Temperature:510℃ 
Max Back Pressure:5.1kPa


Fuel System
Fuel System:PT type fuel pump, EFC
100%( Prime Power) Load:198g/kwh
50%( Prime Power) Load213g/kwh


Oil System
Total Oil Capacity:204L
Oil Consumption:≤0.4g/kwh
Engine Oil Tank Capacity:178L
Oil Pressure at Rated RPM:345-483kPa


Cooling System
Cooling Way:Water-cooled
Total Coolant Capacity:300L
Thermostat:82-93℃ 
Max Water Temperature:104℃ 


Alternator Data

Manufacturer:LEROY SOMER/STAMFORD/SIEMENS/MARATHON/ENGGA
Excitation Mode:Brushless and self- exciting
Number of phase and Access Act:3-phase 4-wire
Connecting Type:"Y" type connecting
Alternator Capacity:1500KVA
Alternator Efficiencies:95%
Overload:(PRP)110% load can run 1h
Protection Level:IP22-IP23
Insulation Class, Temperature Rise:H/H
Telephone Influence Factor (TIF):<50
THF:<2%
Voltage Regulation, Steady State:≤±1%
Air Cooling Flow:2.69m3/s
Altitude:≤1000m


Genset Electrical Performance

Voltage Regulation:≥±5%
Voltage Regulation, Stead State:≤±1%
Sudden Voltage Warp (100% Sudden Reduce):≤+25%
Sudden Voltage Warp (Sudden Increase):≤-20%
Voltage Stable Time (100% Sudden Reduce):≤6S
Voltage Stable Time (Sudden Increase):≤6S
Frequency Regulation, Stead State:≤5%
Frequency Waving:≤1.5%
Sudden Frequency Warp (100% SuddenReduce):≤+12%
Sudden Frequency Warp (Sudden Increase):≤-10%
FrequencyRecoveryTime(100%SuddenReduce):≤5S
FrequencyRecoveryTime(Sudden Increase):≤5S


Options

Engine

Alternator

Heater 2KW & 4KW

Anti Condensation Heater

Battery Charger 3.5A & 7A

Permanent Magnet Generator(PMG)

Water Separator

Drop CT(For Paralleling)

Daily Fuel Tank

 

Fuel Level Sensor

 

Control System

Others

Remote Control Panel

Rainproof Type

Auto Transfer Switch (ATS)

Soundproof Type

Paralleling System

Trailer Type

Open Type

Overall Size

Weight

5200(mm)*2000(mm)*2300(mm)

12000(kg)

Cummins 1200 GF.png

Soundproof Type

Overall Size

Weight

7000(mm)*2400(mm)*2900(mm)

18500(kg)


Cummins 1200 GF.png

Standard Control Panel

Cummins 1100GF 

Dingbo Standard Control Panel uses micro processing technique integrating digital, intelligent and network techniques which can carry out functions including auto start/stop, data measure, alarming. The controller uses LCD display, optional Chinese and English display interface with operation easy and reliable. It can be widely used in all types of generator automatic control system for compact structure, advanced circuits, simple connections and high reliability


Auto Module Control Panel

Cummins 1100GF 

Auto Module Control Panel is the configuration for nobody on duty controlling generators. This kind of panel adopts auto module control system, with large LCD display to show the menu. Features: 6110 can receive remote output signal from ATS and realize auto start and stop of generators. 6310 can realize all functions of 6110, add RS232 interface which can communicate with PC to realize remote operation. 6410 Auto Mains Failure controller, can realize all functions of 6310, furthermore can detect ATS and control directly.

Auto Parallel Control Panel

Cummins 1100GF

This new automatic parallel system adopts intelligent modules, inserted and folded installed, no need the peripheral relay and logic circuit. The main switch adopts electronic breaker or frame breaker, combined together with the generator, which is very reliable. One generator, one panel. The panel can be used both for singly and parallel. It is only need to parallel generator with such panel when the capability needs to be enlarged in the future.


150KW 187.5kVA Cummins Diesel Generator Set
50KW 62.5kVA Cummins QSB3.9-G35 Diesel Generator Set
230kw 288kva Cummins Diesel Generator Set

Contact Us

  • Add.: No. 10 Kechuang Road, High tech Zone, Nanning, Guangxi, China
  • Tel.: +86 771 5805 269
  • Fax: +86 771 5805 259
  • Cellphone: +86 134 8102 4441
                    +86 138 7819 8542
  • E-mail: [email protected]
Follow Us

Copyright © Guangxi Dingbo Generator Set Manufacturing Co., Ltd. All Rights Reserved | Sitemap

Update cookies preferences

generator set:

Emergency vs Standby Generator: What’s The Difference? Commercial Generators Trailer Mounted Water Pumps for Sale
Contact Us